FIND SALES & SERVICE

GL-11000-USA

GL Series

  • Prime Output 10.0 kVA (10.0 kW)
  • Standby Output 11.0 kVA (11.0 kW)
  • Frequency: 60 HZ
  • Phase: Single
Features & Benefits
Specifications

Improved Reliability

  • Generator and engine are direct-coupled to ensure a more reliable power supply with minimum power loss.
  • Large-capacity fuel tank (28L/7.4 U.S. gal.) enables longer continuous operation on a single tank.

Easy Maintenance

  • One-side maintenance to reduce the operator’s work load.
  • Larger-capacity oil pan employed to stretch the oil change intervals up to 200 operating hours. Reduces the running cost for the generator owner.

Safety Features

  • Protective covers on all moving parts (for the engine’s cooling fan and the generator).
  • Automatically shuts the engine down in case the water temperature rises excessively or the oil pressure drops below a safe level.

Wide Application

  • Double element air cleaners are standard equipment. Ideal for heavy-duty application in dusty environments.
  • An access terminal to connect to the ATS (Automatic Transfer Switches) is standard equipment. Applicable for stationary use as well.
MODELUnitGL-11000
Type-Rotating field single-phase AC generator
FrequencyHz 60
Standby OutputkVA (kW)11.0 (11.0)
Prime OutputkVA (kW)10.0 (10.0)
Voltage - Single PhaseV110/220
Armature Connection-Series
Phase / Wire- 1/3
Power Factor-1.0
No. of Poles-2
InsulationClassRotor coil; class F, Stator coil; class B
Type of Coupling-Direct coupled
AMPS
Single Phase 110VA90.9
Single Phase 220VA45.5
NO. OF RECEPTACLES
5-15R-2
5-20RA (GFCI)-N/A
L5-30R-N/A
L6-30R- N/A
L14-30R-N/A
CS-6369- N/A
TERMINAL
Terminal- Available
DIESEL ENGINE
Type-Vertical, water-cooled, 4-cycle diesel engine
Model-D722
No. of Cylinders-3
Bore x Strokemm (in.)67.0 x 68.0 (2.6 x 2.7)
DisplacementL (cu. in.)0.719 (43.9)
Engine Speedrpm3600
Continuous Rated OutputkW (HP)12.2 (16.3)
Lubricant (API classification)-Above CD grade
Oil CapacityL (qts.)3.4 (0.9)
Coolant CapacityL (qts.)4.1 (1.1)
Starting System-Electric - 12 volt DC
SET
Fuel Consumption-Diesel fuel No.2 (ASTM D975)
at Full LoadL/h (gal./h) 4.1 (1.09)
at 3/4 LoadL/h (gal./h)3.3 (0.86)
at 1/2 LoadL/h (gal./h)2.7 (0.71)
at 1/4 Load L/h (gal./h) 2.2 (0.59)
Fuel Tank Capacity Continuous Operation Hours Continuous Operation HoursL (gal.)28.0 (7.4)
at Full Loadh7.0
at 3/4 Loadh8.5
at 1/2 Loadh10.4
at 1/4 Loadh12.7
Battery (Ah/5 h)-55B24R (12 V x 36 Ah)
Dimensions L x W x Hmm (in.)1281 x 618 x 698 (50.4 x 24.3 x 27.5)
Approx. Net Weightkg (lbs.)295 (650)
Sound Level (Full Load at 23 ft. [7m])dB (A)68
Emergency Stop System-In case of abnormal: Oil pressure, water temperature, or When the access terminal cover is opened